Fire pump controller acc. to NFPA-20 and/or FM/UL-Approval

We manufacture and deliver fire pump controller for different requirements according to the international accepted fire pump standard NFPA-20 with the following features:

  • Fire pump controller for diesel and electric driven fire pumps
  • Voltage between 0,23 and 7,2 kV
  • Fire pump controller with or without approval and acceptance by FM and /or UL
  • Fire pump controller manufactured according to customer requirements

 

Controller for diesel engine driven fire pump units

Standard Features

  • solid steel plate enclosure
  • standard version for use with lead acid batteries
  • special versions for use with nickel-cadmium batteries are available
  • battery voltage 12 V DC or 24 V DC
  • supply voltage 1~230, 3~400 V, 50 Hz or 1-110/120 V, 60 Hz (extra voltages on request)
  • circuit configuration and switching functions conforming to NFPA-20

Diesel controller type FD4e


  • FM approved for the use with fire fighting equipment conforming to NFPA-20
  • CE Marking
  • microprocessor based controller intended for starting and monitoring NFPA fire pump diesel engines
  • alphanumeric display showing alarm and mode indications featuring user control pushbuttons for operation
  • additional annunciation LED’s with inscribable labels for alarm and mode indications
  • internal memory for several thousand events, equipped with SD memory card for easy data analysis by PC
  • 4 – 20 mA pressure transducer for the recording of the system pressure and switching of the pump unit
  • with high-performance, microprocessor controlled battery chargers
  • several NEMA type enclosures available as well as enclosure completely made of stainless steel

Diesel controller type FD4eU


  • suitable for the use with fire fighting equipment conforming to NFPA-20
  • CE Marking
  • microprocessor based controller intended for starting and monitoring NFPA fire pump diesel engines
  • suitable for diesel engines without instrument panel
  • equipped with all displays required by NFPA-20 for diesel engines, such as
    • engine hours meter
    • tachometer
    • oil pressure
    • water temperature
    • speed recording and evaluatio
  • alphanumeric display showing alarm and mode indications featuring user control pushbuttons for operation
  • additional annunciation LED’s with inscribable labels for alarm and mode indications
  • internal memory for several thousand events, equipped with SD memory card for easy data analysis by PC
  • 4 – 20 mA pressure transducer for the recording of the system pressure and switching of the pump unit
  • with high-performance, microprocessor controlled battery chargers
  • several NEMA type enclosures available as well as enclosure completely made of stainless steel

 

Controllers for electric motor driven fire pump units (Low Voltage)

Standard Features

  • solid steel plate enclosure
  • for power ranges from 3~200 to 600 V, 50 – 60 Hz (extra voltages on request)
  • motor ratings from 2 to 521 kW
  • special design with automatic power transfer switch available second utility emergency supply or generator set emergency supply
  • circuit configuration and switching functions conforming to NFPA-20

Type MP300 Direct on line (Fig. with legs for floor mounting)


  • FM approved for the use with fire fighting equipment conforming to NFPA-20
  • CE Marking
  • fully automatic, pressure independent operation, manual stop
  • Microprocessor based controller intended for starting and monitoring NFPA electric motor driven fire pumps
  • alphanumeric display showing alarm and mode indications featuring user control pushbuttons for operation
  • additional annunciation LED’s with inscribable labels for alarm and mode indications
  • internal memory for several thousand events, equipped with SD memory card for easy data analysis by PC
  • 4 – 20 mA pressure transducer for the recording of the system pressure and switching of the pump unit
  • several NEMA type enclosures available as well as enclosure completely made of stainless steel

Electric fire pump controller type MP430 with wye/delta starting (with open circuit transition)


  • FM approved for the use with fire fighting equipment conforming to NFPA-20
  • CE Marking
  • fully automatic, pressure independent operation, manual stop
  • Microprocessor based controller intended for starting and monitoring NFPA electric motor driven fire pumps
  • alphanumeric display showing alarm and mode indications featuring user control pushbuttons for operation
  • additional annunciation LED’s with inscribable labels for alarm and mode indications
  • internal memory for several thousand events, equipped with SD memory card for easy data analysis by PC
  • 4 – 20 mA pressure transducer for the recording of the system pressure and switching of the pump unit
  • several NEMA type enclosures available as well as enclosure completely made of stainless steel

 

Controllers for electric motor driven fire pump units (Medium Voltage)

Standard Features

  • solid steel plate enclosure
  • for power ranges from 3~2.400 to 6.600 V, 50 – 60 Hz (extra voltages on request)
  • motor ratings from 200 to 3.000 HP (149 to 2.239 kW)
  • circuit configuration and switching functions conforming to NFPA-20

Type MP600 Direct on line (Fig. with legs for floor mounting)


  • FM approved for the use with fire fighting equipment conforming to NFPA-20
  • CE Marking
  • fully automatic, pressure independent operation, manual stop
  • Microprocessor based controller intended for starting and monitoring NFPA electric motor driven fire pumps
  • alphanumeric display showing alarm and mode indications featuring user control pushbuttons for operation
  • additional annunciation LED’s with inscribable labels for alarm and mode indications
  • internal memory for several thousand events, equipped with SD memory card for easy data analysis by PC
  • 4 – 20 mA pressure transducer for the recording of the system pressure and switching of the pump unit
  • several NEMA type enclosures available as well as enclosure completely made of stainless steel

 

Controller for Jockey Pumps (Low Voltage)

Standard Features

  • solid steel plate enclosure
  • for power ranges from 3~200 to 600 V, 50 – 60 Hz (extra voltages on request)
  • motor ratings from 0,25 to 50 HP (0,18 to 37 kW)
  • circuit configuration and switching functions conforming to NFPA-20

Type M15A Direct on line


  • UL approved for automatic operation in industrial installations
  • CE Marking
  • fully automatic, pressure independent operation, manual stop
  • pressure switch for the recording of the system pressure and switching of the pump unit
  • several NEMA type enclosures available as well as enclosure completely made of stainless steel